REVERSE OSMOSIS

HOME | REVERSE OSMOSIS | CONTROLLERS | REVERSE OSMOSIS CONTROLLERS

REVERSE OSMOSIS CONTROLLER - OS3015

Reverse Osmosis Controller – OS3015 (excluding conductivity meter, 3 inputs and 3 outputs). The unit type OS3015 is universal applicable for automatic monitoring and control of reverse osmosis plants. The controller is not equipped with an conductivity meter. There are four possible stages : “Stand by”, “Production”, “Rinse after production” and “Rinse during standby”. This unit can monitor conductivity and several inputs e.g. level switches, low pressure switch, exceeded pressure and stop. Adaptable to user specific requirements by built-in programmable options. The programmed configuration will be stored into non volatile memory and therefore not be affected by power loss.

  • User operated programming using double row of illuminated LCD display
  • Display text in English, French, German, Italian, Spanish or Dutch.
  • Adaption to user specific requirements by means of options programmable on site
  • 4 programmable stages (Production, Stand-by, Rinse after production, Interval rinse during Standby).
  • Extensive status report facility using information button.
  • 2 inputs : low water pressure and tank full
  • 1 programmable input for : stop, excess pressure or tank empty.
  • 2 outputs: Inlet valve (fused 8A), High pressure pump (fused 8A).
  • 1 programmable potential free output: Alarm or concentrate valve.
  • Secure from power failure as all data is stored long-term without battery.
  • Efficient micro controller with watchdog, illegal operation code and cycle monitoring.
  • Safeguarded from EMC by galvanic separation between microcontroller and in- and output circuits and also by additional interference suppression filter
  • Available for wall-mounting.
  • Available (input /output) : 12VDC/12VDC, 24VDC/24VDC, 24VAC/24VAC, 115VAC/115VAC, 230VAC/230VAC
os3015 user manual

REVERSE OSMOSIS CONTROLLER - OS3020

The unit type OS3020 is universal applicable for automatic monitoring and control of reverse osmosis plants. The controller is equipped with an conductivity meter without temperature meter. There are four possible stages : “Stand by”, “Production”, “Rinse after production” and “Rinse during standby”. This unit can monitor conductivity and several inputs e.g. level switches, low pressure switch, exceeded pressure and stop. Adaptable to user specific requirements by built-in programmable options. The programmed configuration will be stored into non volatile memory and therefore not be affected by power loss.

  • User operated programming using double row of illuminated LCD display.
  • Display text in English, French, German, Italian, Spanish, Swedish, Czech or Dutch.
  • Adaption to user specific requirements by means of options programmable on site
  • 4 programmable stages (Production, Stand-by, Rinse after production, Interval rinse during Standby).
  • Extensive status report facility using information button.
  • 2 inputs : low water pressure and tank full
  • 1 programmable input for : stop, excess pressure or tank empty.
  • 2 powered relay outputs: Inlet valve (fused 8A), High pressure pump (fused 8A).
  • 1 relay output (dry contact) : programmable for Alarm or Concentrate valve.
  • Secure from power failure as all data is stored long-term without battery.
  • Efficient micro controller with watchdog, illegal operation code and cycle monitoring.
  • Safeguarded from EMC by galvanic separation between microcontroller and in- and output circuits and also by additional interference suppression filter
  • Available for wall-mounting.
  • Available (input /output) : 12VDC/12VDC, 24VDC/24VDC, 24VAC/24VAC, 115VAC/115VAC, 230VAC/230VAC
os3020 user manual
Reverse Osmosis Controller – OS3020 (including conductivity cell, 3 inputs and 3 outputs).
ModelPower in / out
OS302024, 115 or 230 VAC
OS3020DC12 or 24 VDC

reverse osmosis controller - OS3030

The unit type OS3030 is universal applicable for automatic monitoring and control of reverse osmosis plants. The controller is equipped with an conductivity meter without temperature meter. There are six possible stages : “Stand by”, “Production”, “Rinse after production”, “Rinse during standby”, “Rinse during production” and “Maintenance”. Adaptable to user specific requirements by built-in programmable options. The programmed configuration will be stored into non volatile memory and therefore not be affected by power loss.

  • User operated programming using double row of illuminated LCD display.
  • Display text in English, French, German, Italian, Spanish, Czech or Dutch.
  • Simple control utilising easy to follow symbols.
  • Built-in audio signal for 12 programmable signal indicators.
  • Adaption to user specific requirements by means of options programmable on site.
  • Simple operation by means of a few clear operating symbols.
  • Can be used for various sizes of plant.
  • 10 programmable stages with several steps in some cases: production, stand-by, rinse after production, rinse during extraction, rinse during stand-by, stop when producing, stop when rising, stop when breakdown, maintenance and stop for maintenance.
  • Desalinated water production controlled manually or using level switch.
  • Locking of maintenance setting and programming possible by use of code number.
  • Input of service telephone number.
  • Extensive status report facility using information button.
  • 2 inputs: container full and container empty.
  • 2 programmable inputs: stop, excess pressure, concentrate, ext. signal switch or low water level.
  • 1 optional programmable input (IF circuit board).
  • Inputs programmable active open or closed.
  • Optional installation of safety switch for high pressure pump.
  • 1 connection for conductivity sensor (cell constant programmable from 0,01 to 10,00 cm-1).
  • Manual temperature compensation.
  • 3 Outputs: High pressure pump, inlet valve, and concentrate rinse valve.
  • 2 optional programmable outputs: dosing, extra program, permeate valve or indicator relay (IF circuit board).
  • Output relay programmable active under current or not under current.
  • Secure from power failure as all data is stored long-term without battery.
  • Efficient micro controller with watchdog, illegal operation code and cycle monitoring.
  • Safeguarded from EMC by galvanic separation between microcontroller and in- and output circuits and also by additional interference suppression filter.
  • Available for wall-mounting.
  • Available (input /output) : 24/24VAC, 115/115VAC, 230/230VAC, 115/24VAC, 230/24VAC
os3030 user manual
Reverse Osmosis Controller – OS3030 (1 conductivity meter, man. Temp. Comp. 4 inputs and 3 outputs).
ModelPower in / out
OS303024/24, 115/115 or 230/230 VAC
OS3030115/24 or 230/24 VAC
Reverse Osmosis Controller – OS3030IF (1 conductivity meter, man. Temp. Comp. 5 inputs and 5 outputs).
OS3030IF24/24, 115/115 or 230/230 VAC
OS3030IF115/24 or 230/24 VAC

REVERSE OSMOSIS CONTROLLER OS3050 / 51

The unit type OS3050 or type OS3051 is universal applicable for automatic monitoring and control of reverse osmosis plants. The controller is equipped with a conductivity meter optional is a second conductivity meter and temperature meter. Also optional is a circuit board with two recorder outputs (0(4) – 20 mA). There are five possible stages : “Stand by”, “Production”, “Rinse after production”, “Rinse during standby” and “Maintenance”. Adaptable to user specific requirements by built-in programmable options. The programmed configuration will be stored into non volatile memory and therefore not be affected by power loss.

  • Menu driven programming utilising “two line” LCD-display
  • Choice of languages (English, French, German, Italian, Spanish or Dutch)
  • Adaptable to user specific requirements by built-in programmable options.
  • Simple control utilising easy to follow symbols.
  • Universally applicable for various sizes of installation
  • Desalinated water production controllable by hand or level switches
  • Control of the maintenance situation by means of a code choice possible
  • Programming a service telephone number possible
  • Substantial status information employing INFO key: actual input and output conditions, service telephone number, software version, programming situation of the annunciation and malfunction relays, rinse interval, rinse times, instrument probe cell constants
  • Large green LED-display showing permeate- and raw water conductivity plus the relative
  • Permeate-conductivity as a percentage value of the raw water conductivity or raw water temperature
  • Optional card for 2 recorder outputs 0(4)-20mA (conductivity / temperature)
  • Input: production-stop, storage tank full/empty, excess pressure, low pressure, concentrate-monitoring or alarm reset, motor protection switch, temperature feeler (optional)
  • Integrated conductivity meter with automatic range switching
  • Conductivity range according to the instrument probe cell constants from 0,1 to 1 00 000 µS/cm
  • The instrument probe cell constants programmable from 0,01 to 10,00 cm-1
  • Manual or automatic temperature compensation
  • Duplicate conductivity meter and temperature reading as an available option
  • Thermo switch with annunciation contact for 115/230 Volt pressure pump as available option Output: pressure pump (protection), input valve, rinse valve for concentrate and permeate, annunciation and malfunction contact
  • Security of program information against supply failure, as all program information is stored without accu
  • Large capacity microprocessor with “Watchdog”, illegal “Operation code” and frequency monitoring
  • Manufactured in accordance with EMC codes of practice; by means of galvanic isolation between the micro-processor and the in- and output circuits, plus extra built-in filter
  • Available for wall-mounting and panel-mounting
  • Available (input /output) : 24/24V, 115/115V, 230/230V
os3050/51 user manual
Reverse Osmosis Controller – OS3050/1 (1 conductivity meter, man. Temp. Comp. 7 inputs and 7 outputs).
ModelPower in / out
OS3050/124/24, 115/115 or 230/230 VAC
Reverse Osmosis Controller – OS3050/2 (1 conductivity meter, man. Temp. Comp. 7 inputs and 7 outputs).
OS3050/224/24, 115/115 or 230/230 VAC
Reverse Osmosis Controller – OS3050/1/l (as OS3050/1 and including 2 recorder outputs ).
OS3050/1/124/24, 115/115 or 230/230 VAC
Reverse Osmosis Controller – OS3050/2/l (as OS3050/2 and including 2 recorder outputs ).
OS3050/2/l24/24, 115/115 or 230/230 VAC
Reverse Osmosis Controller – OS3051/1 (1 conductivity meter, man. Temp. Comp. 7 inputs and 7 outputs).
OS3051/124/24, 115/115 or 230/230 VAC
Reverse Osmosis Controller – OS3051/2 (2 conductivity meter, aut. Temp. Comp. 7 inputs and 7 outputs).
OS3051/224/24, 115/115 or 230/230 VAC
Reverse Osmosis Controller – OS3051/1/1 (As OS3051/1 and including 2 recorder outputs).
OS3051/1/124/24, 115/115 or 230/230 VAC
Reverse Osmosis Controller – OS3051/2/l (As OS3051/2 and including 2 recorder outputs).
OS3051/2/l24/24, 115/115 or 230/230 VAC

REVERSE OSMOSIS CONTROLLER RGS3000

The unit type RGS3000 is universal applicable for automatic monitoring and control of reverse osmosis plants. There are six possible stages : “Stand by”, “Production”, “Rinse after production”, “Rinse during production”, “Rinse during standby” and “Maintenance “. This unit can monitor conductivity, temperature and several inputs e.g. level switches, low pressure switch, motor security switch, etc.. Adaptable to user specific requirements by built-in programmable options. The programmed configuration will be stored into non volatile memory and therefore not be affected by power loss.

  • Choice of languages (English, French, German and Dutch)
  • Graphic LCD display (128×64) with easy to use menu
  • Adaptable to user specific requirements by built-in programmable options.
  • Universally applicable for various sizes of installation
  • Desalinated water production controllable by hand or level switches
  • Control of the maintenance situation by means of a code choice possible
  • Programming a service telephone number possible
  • Substantial status information: actual input and output conditions, service telephone number, alarm history, software version
  • Integrated conductivity meter with automatic range switching.
  • Conductivity range according to the instrument probe cell constants from 0,1 to 100.000 µS/cm
  • The instrument probe cell constants programmable from 0,01 to 10,00 cm-1
  • Manual or automatic temperature compensation
  • Security of program information against supply failure.
  • 1x Outputs (powered) programmable for output function e.g. inlet valve, high pressure pump, concentrate valve, permeate valve.
  • 4x Outputs (configurable as powered or potential free) programmable for output function e.g. inlet valve, high pressure pump, concentrate valve, booster pump / alarm (programmable for booster pump or alarm), alarm.
  • 5x inputs (digital contacts): stop, high level switch, low level switch, exceeded pressure switch, low pressure switch, concentrate flow switch, motor security switch, external alarm reset switch, regeneration indication, level switch dosing tank.
  • SD Card functions for software updates, data log and loading and saving of configuration.
  • Option : RS485 communication for log data
  • Option : Ethernet communication for web server, e-mail function and remote control
RGS3000 manual
Reverse Osmosis Controller – RGS3000 (conductivity meter, auto Temperature Comp. 4 inputs and 3 outputs).
ModelPower in / out
RGS3X00 (basic)24/24, 115/115 or 230/230 VAC
RGS3X00 (basic)115/24, 230/24 or 240/24 VAC
RGS3X01 (basic and 1 additional input, and 2 additional outputs)24/24, 115/115 or 230/230 VAC
RGS3X01 (basic and 1 additional input, and 2 additional outputs)115/24, 230/24 or 240/24 VAC
RGS3X12 (RGS3x01 and ethernet and RS485)24/24, 115/115 or 230/230 VAC
RGS3X12 (RGS3x01 and ethernet and RS485)115/24, 230/24 or 240/24 VAC

reverse osmosis controller - RGS8000

The unit type RGS8000 is universal applicable for automatic monitoring and control of reverse osmosis plants. There are six possible stages : “Stand by”, “Production”, “Rinse after production”, “Rinse during production”, “Rinse during standby” and “Maintenance “. This unit can monitor conductivity, temperature and several inputs e.g. level switches, low pressure switch, motor security switch, etc.. Adaptable to user specific requirements by built-in programmable options. The programmed configuration will be stored into non volatile memory and therefore not be affected by power loss.

  • Choice of languages (English, French, German and Dutch).
  • Graphic TFT display (800×480, touch panel) with easy to use menu
  • Adaptable to user specific requirements by built-in programmable options.
  • Universally applicable for various sizes of installation.
  • Desalinated water production controllable by hand or level switches.
  • Control of the maintenance situation by means of a code choice possible
  • Programming a service telephone number possible
  • Substantial status information: actual input and output conditions, service telephone number, alarm history, software version
  • Integrated conductivity meter with automatic range switching.
  • Conductivity range according to the instrument probe cell constants from 0,1 to 100.000 µS/cm
  • The instrument probe cell constants programmable from 0,01 to 10,00 cm-1
  • Manual or automatic temperature compensation
  • Security of program information against supply failure.
  • 4x Outputs (powered) programmable for output function e.g. inlet valve, high pressure pump, concentrate valve, permeate valve.
  • 3x Outputs (potential free) programmable for output function e.g. inlet valve, high pressure pump, concentrate valve, booster pump / alarm (programmable for booster pump or alarm), alarm.
  • 8x inputs (digital contacts): stop, high level switch, low level switch, exceeded pressure switch, low pressure switch, concentrate flow switch, motor security switch, external alarm reset switch, regeneration indication, level switch dosing tank.
  • Option : up to 4 conductivity meters and temperature input
  • Option : up to 6 Recorder outputs 0(4)-20mA for recording measurements
  • Option : up to 12 Inputs 0(4)-20mA for flow meters, pressure meters, conductivity meters and tank level measurement
  • Option : Extra relay card with 4 powered outputs and 3 potential free outputs, free programmable
  • SD Card functions for software updates, data log and loading and saving of configuration.
  • Option : RS232 and RS485 communication for log data
  • Option : Ethernet communication for web server, e-mail function and remote control
  • Enclosure suitable for wall mounting, panel mounting and plate mounting
  • Available supply voltage (input/output) : 24V, 230V, 115/24V, 230/24V and 240/24V.
RGS8000 manual
Reverse Osmosis Controller – RGS8000 (conductivity meter, auto Temperature Comp. 8 inputs and 7 outputs).
ModelPower in / out
RGS8x01-1000-0no Ethernet, RS232 and RS485
RGS8x11-1000-0with Ethernet, RS232 and RS485
Industrial Water Equipment Recommended Products
IWE Compact IBC RO

IWE Compact IBC RO – 150 lph

£2,368.00 (exc. VAT)

IWE Brackish Water RO Membrane

IWE 40 40 Brackish Water Membrane – 4″ x 40″

£160.83 (exc. VAT)

6 Stage RO Filter for Domestic Use

6 Stage Pumped Reverse Osmosis Unit

£254.95 (exc. VAT)

RO Broad Spectrum Antiscalant

25 Kg Broad Spectrum Antiscalant

£84.75 (exc. VAT)

Need Help?

We can advise on the correct controller for your application, please contact our sales department on :

01629 363311

We are more than happy to help.