You are here : Home | Products & Systems | Water Filters | UV Water Filters | IWE Range | SDE


[one_fourth padding=”0 6px 0 0″]

Quick Selection Header

IWE UV Water Filters

SDE Range

1.8 l/min

3.7 l/min

7.5 l/min

22.7 l/min

30 l/min

45 l/min

[su_spacer]

ST08 Range

11 l/min

26.5 l/min

45 l/min

75 l/min

[su_spacer]

SPS Range

WM 30 l/min

WM 45 l/min

FS 30 l/min

FS 45 l/min

[su_spacer size=”100″]

[/one_fourth] [three_fourth_last padding=”0 0px 0 0″]

SDE Range Installation Manual & Operating Instructions

 

IWE SDE RANGE
SDE Range UV Water FiltersSDE Range UV Filter Kits
Installation ManualCE Certificate
Dimensions

 [su_spacer size=”20″]

Installation, Operation and Maintenance Manual 

For IWE SDE Series Ultraviolet Disinfection Water System

 [su_spacer size=”20″]

symbol1Risk of severe or fatal electrical shock when water is in close proximity to this electrical system. User must always disconnect power before performing any maintenance on this system.
symbol2This UV system must be grounded.
symbol3Always wear protective eye and skin wear. Germicidal ultraviolet rays are harmful to the eyes and skin, exposure should be avoided.
symbol4CAUTION: Risk of burning due to heat from the lamp when in use. Never touch the lamp directly; we advise always wearing protective gloves.

Thank you for purchasing an Industrial Water Equipment ultraviolet disinfection water system. This manual will help you get the very best from your new system. It covers the installation, operation and maintenance of your new UV system.

PLEASE READ ALL THE INSTRUCTIONS CAREFULLY BEFORE BEGINNING TO INSTALL OR TURN ON THE EQUIPMENT. THIS IS TO KEEP YOU AND THE EQUIPMENT SAFE.

Name

SDE Stainless Steel Ultraviolet Disinfection System

Applications

Industrial, medical, food processing, algae in water, viruses, bacteria

Function

Disinfect bacteria, moulds, viruses, algae in water.

Power consumption

8w – 72w

Input

110V or 220v 50/60 Hz

sde-manual1

System Installation

Step 1

Check the package contents to ensure all components are present.

The contents should include:

  • Reactor Chamber
  • UV Lamp
  • Quartz Sleeve
  • Electronic Ballast
  • Support

sde-manual2

Step 2

Make sure the Quartz sleeve and UV bulb are both clean. These can be cleaned with mild detergent or alcohol if required.

Wear soft non abrasive gloves when handing either the Quartz Sleeve or UV Lamp.

Step 3

Remove the open and closed end nut from the reactor chamber.

sde-manual3

Step 4

Place the o-ring onto the open end of the quartz sleeve. The o-ring should be placed roughly around 12mm from the edge of the open end of the sleeve.

sde-manual4

Step 5

Carefully place the Quartz sleeve into the UV chamber.

sde-manual5

Step 6

Install the o-ring onto the closed end of the Quartz sleeve.

sde-manual6

Step 7

Screw the closed end nut onto the closed end of the UV chamber, do not over tighten. Hand Tight is sufficient.

sde-manual7

Step 8

Screw the open end nut onto the open end of the UV chamber, do not over tighten. Hand Tight is sufficient.

sde-manual8

Step 9

Connect the 2-pin power cable to the UV Lamp ensuring a secure connection.

sde-manual9

Step 10

Carefully insert the UV bulb into the Quartz sleeve through the open end.

sde-manual10

Step 11

Hand tighten the open end cover cap onto the open end nut.

sde-manual11

Step 12

Choose a well lit and easily accessible location to install your UV water Filter. The chamber can be installed either in a horizontal or vertical position.

Step 13

When all plumbing connections are complete slowly turn on the water supply keeping a check on any leaks.

Step 14

Allow the water to run through the UV filter for a few minutes to clear any air or debris from within the UV chamber.

Step 15

Connect the power cable to the UV unit.

Water quality

The SDE UV Water Filter is designed for use on visually clear water, not coloured, turbid or cloudy.

  • Ambient Water Temperature: 2-45℃
  • Iron: <0.3ppm (0.3mg/l)
  • Hardness: <7gpg (120mg/l)
  • Turbidity: <1NTU
  • Manganese: 0.05ppm (0.05mg/l)
  • UV Transmittance: >75%

Recheck all connections prior to powering on the UV filter.

Should the UV Lamp or Quartz sleeve become damaged please power off the unit and replace the required parts.

Your SDE UV Water Filter is designed for continuous operation. Frequent powering on and off of the system will dramatically reduce the lifespan of the UV lamp.

If your UV filter becomes submerged in water power off the unit and retrieve. Please contact Industrial Water Equipment for further advice.

Do not operate your UV water filter if it has been dropped or damaged in any way.

Your UV system should be installed after the filter on the return line.

Always disconnect the UV from power and drain down if the unit is going to be subjected to temperatures below 0ºC for a prolonged period of time.

Important Safeguards

symbol1Risk of severe or fatal electrical shock when water is in close proximity to this electrical system. User must always disconnect power before performing any maintenance on this system.
symbol2This UV system must be grounded.
symbol3Always wear protective eye and skin wear. Germicidal ultraviolet rays are harmful to the eyes and skin, exposure should be avoided.
symbol4CAUTION: Risk of burning due to heat from the lamp when in use. Never touch the lamp directly; we advise always wearing protective gloves.

System Maintenance

Monthly visual inspection for any signs of damage.

UV Bulbs should be replaced after 9000 hrs of operation. The lamp may still function after this period of time, however the UV intensity will be greatly diminished and therefore should be replaced.

Clean the Quartz sleeve every 3-6 months. This can be done with either alcohol or a mild detergent.

[/three_fourth_last]